상단메뉴 바로가기 본문 바로가기 본문 하위메뉴 바로가기 하단 바로가기

HY-ALERTA™ 2620
HY-ALERTA™ 2620
CatalogH2scan-Safety-Products-Data-Sheet-90000009R3.pdf
내용

HY-ALERTA™ 2620

Explosion Proof Area Hydrogen Monitor



H2scan’s 2620 Explosion Proof Area Hydrogen Monitor provides hydrogen-specific leak detection and measurement for hydrogen concentrations as low as 4000 ppm and can be scaled to any concentration up to 5% hydrogen by volume, a range representing 10% to 125% of hydrogen’s low flammability limit. The monitor is designed for either ceiling or wall mount. H2scan’s hydrogen-specific sensor technology has no cross sensitivity to other combustible gases, thus eliminating false positive alarms and ensuring safety system reliability.



Configuration Details

Performance

  • Hydrogen Sensitivity Range: 0.4% to 5.0% hydrogen by volume, 10% to 125% hydrogen lower flammable limit
  • Response Time: T90 < 60 sec
  • Ingress Protection: IP64 capable
  • Calibration Interval: 90 days
  • Product Life Expectancy: 10 years
  • Accuracy: ± (3% of reading + 0.2) percent hydrogen by volume 


Interface Options

  • Input Voltage Range: 90 VAC to 240 VAC
  • Input Power: 15W
  • Analog Outputs:
  • Output Currents
    • – 4 mA to 20 mA
    • – 0 mA to 20 mA
    • – User-specific mA range
  • Serial Communication Options: RS232 or RS422
  • Relay Contacts: Two programmable relays and one fault relay with both normally open (N.O.) and normally closed (N.C.) contacts:
    • – 5A/240VAC
    • – 5A/ 30 VDC 


Dimensions

  • Width: 13.8 cm (5.4 in)
  • Length: 19.2 cm (7.5 in)
  • Depth: 13.0 cm (5.7 in) 


Operating Conditions

  • Operating Temperature Range: -20ºC to 55ºC
  • Storage Temperature Range: -30ºC to 80ºC
  • Operating Humidity: 0% to 95% RH (non-condensing)
  • Calibration Background Gas: Air 


Adapter Fittings

  • 1/4 in. Tube for Calibration Gas Connection



Certifications


 


2620

  • UL 508, 1203
  • USC – Class I, Division 1, Groups B, C, and D Hazardous (Classified)

  •  

Remote

  • UL 913
  • CAN/CSA C22.2 No. 157-92

  •  


HY-ALERTA™ is a registered Trademark of H2scan.

Specifications subject to change without prior notice.

상세 이미지

  • dwyer
  • tescom
  • hoke
  • bronkhorst
  • blue-white
  • manostar
  • h2scan
  • ctc
  • circleseal controls
  • apollo valves
  • danfoss hansen